Tuesday, June 25, 2013

Calculating Short Circuit Currents (SCC)

In my last blog post (which was much too long ago), I wrote that the National Electric Code (NEC) requires the equipment be “selected and coordinated to permit the circuit protective devices used to clear a fault to do so without excessive damage to the electrical equipment of the circuit” [1].  To achieve a safe condition requires that equipment connected to the electrical system have short circuit current rating (SCCR).

To ensure that the equipment is being installed such that the calculated or tested SCCR is sufficient, a short circuit current (fault current) study must be performed.  Short circuit current (SCC) studies can be conducted through hand calculations, or software simulations.  Software simulations are the main method for conducting short circuit current studies.  While there are a number of vendors of this software, EasyPower, SKM, and ETAP seem to be the most used.

To aid engineers or installers when an SCC is not readily available, one can approximate the SCC to determine whether or not the SCCR of the equipment is suitable for the point of application.  The approximation of the SCC can be conducted by referencing the parameters of the closest upstream transformer and conducting some simplistic calculations.

The SCC calculation at the secondary of the transformer can be determined by the power rating of the transformer (P), the full-load secondary current of the transformer (I), the line-line voltage at the secondary of the transformer (V) and the transformer impedance (Z) [2].  The power rating is in kVA, the current is in amperes (A), the voltage is in volts (V), and the transformer impedance is in percent.

The full-load secondary current (I) of the transformer can be calculated by EQ1.

                                                     I = P / (V * SQRT(3))       EQ1

The SCC can be calculated by EQ2

                                                           SCC = I / Z    EQ2
 

 
As an example, suppose that we were going to install an industrial control panel on circuit that was supplied from a 500 kVA transformer with a voltage of 480 V, 3W+G, and an impedance of 3 %.  Using EQ1 and EQ2 yields a short circuit current of 20.05 kA.  To properly apply the industrial control panel, the equipment is required to have an SCCR that is greater than 20.05 kA. 
 
Common values of equipment SCCR are 5 kA, 10 kA, 14 kA, 22 kA, 25 kA, 30 kA, 42 kA, 50 kA, 65 kA, 85 kA, 100 kA, 125 kA, 150 kA, and 200 kA [3].   
 
An industrial control panel for this application would need to have an SCCR of at least 25 kA.  The SCCR can be calculated using UL508A Supplement SB.
 
This is a simplistic calculation that does not take into account the parameters associated with electrical conductors.  Also, as the power rating (P) of the transformer increases, the available SCC increases.  As the impedance (Z) transformer increases, the available SCC decreases.

Ensuring the equipment is properly applied is the responsibility of engineers and installers.  The NEC requires that equipment have an SCCR that is equal to or greater than the SCC at the point of installation.  Appling an industrial control panel or any other electrical equipment with an SCCR that is less the SCC at the point of installation will compromise the safety of nearby personnel.

REFERNCES.

  1. National Fire Protection Association (NFPA).  National Electric Code, NFPA 70-2011, Quincy, MA USA
  2. McKeown, D., Simple Methods for Calculating Short Circuit Current without a Computer, Retrieved 2012 August 10, Available [on-line] at http://www.geindustrial.com/publibrary/checkout/Short%20Circuit?TNR=White%20Papers|Short%20Circuit|generic.
  3. Underwriters Laboratories (UL).  Standard for Safety Industrial Control Panels, UL 508A, Northbrook, IL USA

10 comments:

  1. Thanks for sharing this really helpful post for calculating short circuit current. I am looking forward for more post of yours.

    For electrical accessories in Dubai visit: Electrical Accessories Dubai

    ReplyDelete
  2. Your blog shares a valuable information about Electrical Safety First's Product Safety Unit attempts to enhance purchaser security by averting mishaps, wounds and passings coming about because of the utilization of electrical items.
    any queries about #ElectricalProductSaftey, plz visit short circuit studies <\a>

    ReplyDelete
  3. This season, Louis Vuitton has released a classic watch series Tambour, naming after the first watch in western—clock-watch Tambour debuted in 1540. Among all the watches, I am especially like this Tambour Heart Watch with Watch PPSC Results On PKResult.

    ReplyDelete
  4. Issara, who played a prominent role in protests last year that helped to overthrow the government of former Prime Minister Yingluck Shinawatra, said Thais should no longer listen to decrees handed down by the Watch Pakistan Result On PkResult.

    ReplyDelete
  5. Mitchell, who is currently on tour with Australia in Sri Lanka, will have to get up early to catch Brandon in the final in Rio which will begin before dawn in Colombo on Wednesday morning -- the last day of the third and final Watch 1st Year Result On PkResult.

    ReplyDelete
  6. India will then welcome New Zealand for three ODIs and three T20 matches, followed by Sri Lanka for a return series with three Tests, three ODIs and three T20s.India are currently touring Sri Lanka. The two sides meet Thursday for the second of Watch Inter Result On PkResult three Tests after the hosts were thrashed in the first, and they then play five ODIs and one T20.

    ReplyDelete
  7. The two are completely separate entities. Even when a watch band is made out of the best materials possible, it can still become damaged and Watch Pakistan Result On PkResult break.

    ReplyDelete
  8. thanks for this useful post on Calculating Short Circuit Currents (SCC)..
    NeboshIGC

    ReplyDelete