From
an electrical safety perspective, the past couple of months have been
interesting. Whether from recent posts
of properly applying Industrial Machines or Industrial Control Cabinets, the number
of electrical safety training programs that I have taught, or the meetings and phone
calls, there are questions around short circuit currents,
fault-currents, short circuit current ratings (SCCR) and why they are
important.
Short
circuit current and fault current are often used interchangeably. However, there are some differences. A short circuit current is an abnormal
condition where two or more conductors of opposite polarity (or ground) are
connected together and where the only limiting impedance is that associated
with the resistive and inductive parameters associated with the electrical
system [1]. Fault current is any
abnormal current that flows in an electrical circuit [2]. Fault current can be from an unintended short
circuit, transient current, overload current, or other abnormal condition.
Short
circuit current rating (SCCR) refers only to equipment or systems and is a
parameter associated with the connection to the electrical system. SCCR is defined as “The prospective
symmetrical fault current at a nominal voltage to which an apparatus or system
is able to be connected without sustaining damage exceeding defined acceptable
criteria” [3].
When
installing electrical equipment or systems (including machines), the National Electric Code requires that
equipment be “selected and coordinated to permit the circuit protective devices
used to clear a fault to do so without excessive damage to the electrical equipment
of the circuit” [3]. Equipment that is
Listed and applied within their Listing requirements are
properly applied [3].
Depending
on the equipment or machine, SCCRs can be determined through testing or through
calculations. Switchboards, switchgear,
panelboards, transfer switch equipment, surge protective devices (SPDs) and the
like require testing to obtain their SCCR.
The SCCR for industrial machines and industrial control cabinets can be
calculated using Underwriter Laboratories Standard
for Safety, Industrial Control Panels,
UL 508A; although these calculations are a result of known practices from tested results.
Listing
agencies (like UL, ETL, TUV, etc.) that conduct testing to determine the SCCR
of equipment are doing so to determine if the equipment is “safe” for
installation and operation at the SCCR.
Within product safety standards, Listing agencies have predetermined pass/fail
criteria. While the pass/fail criteria
vary slightly standard to standard, common examples include [4]:
- Emission of flame, molten metal, glowing or flaming particles through any openings (preexisting or created as a result of the test) in the product.
- Charring, glowing, or flaming of the supporting surface, tissue paper, or cheesecloth.
- Ignition of the enclosure
- Creation of any openings in the enclosure that result in accessibility of live parts, when evaluated in accordance with the accessibility of live parts
- Loss of structural integrity to a degree that the equipment collapses or experiences such displacement of parts that there is a risk of short-circuiting or grounding of current-carrying parts.
- Opening of an external leads or conductors.
Part
of engineering equipment or a system includes not only ensuring that it
functions properly, but also ensuring that it is installed in a manner that
does not create hazardous conditions. Knowing what the short circuit current at the point of installation and the SCCR of the equipment is one step in determining if the equipment is properly applied.
- Wikipedia. Short Circuit Current. Retrieved 2013 March 23. Available [on-line] at http://en.wikipedia.org/wiki/Short_circuit
- Wikipedia. Fault Current. Retrieved 2013 March 23. Available [on-line] at http://en.wikipedia.org/wiki/Fault_(power_engineering)
- National Fire Protection Association (NFPA), National Electric Code, NFPA 70-2011, Quincy, MA USA
- Underwriters Laboratories (UL), Standard for Safety, Surge Protective Devices, UL 1449 3rd edition, Northbrook, IL USA
Hi there, awesome site. I thought the topics you posted on were very interesting. I tried to add your
ReplyDeleteRSS to my feed reader and it a few. take a look at it, hopefully I can add you and follow...
Electrical Calibration
Hi, Great Post, thanks for giving this useful information about SCCR. By checking the SCCR, one can ensure safety and prevention from electrical hazards.
ReplyDeleteFor Domestic Electrical Products visit our website : Domestic Electrical Products Dubai
Thanks for sharing the Useful information !
ReplyDeleteNebosh course in chennai
Nebosh courses in chennai
Nebosh in Chennai
KUALA LUMPUR, May 7 (Reuters) - Malaysia's 1.6 million public servants have long been one of the most reliable vote banks for Prime Minister Najib Razak's ruling coalition, but as he prepares to seek re-election he faces warnings that soaring living costs risk eroding that Watch Jobs Alerts On Jawatankosong.
ReplyDeleteUp north in Georgetown, the capital of Penang, the soul of a Chinatown still lingers after more than 200 years since the founding of the island by Sir Francis Light in 1786. Geographically, the Chinatown is the maze of streets between Lebuh Chula and Jalan Dr. Lim Chwee Watch New Jobs Alerts On Jawatankosong.
ReplyDeleteAdditionally, MNCs with offices in various cities in Canada provide plus salaries and excellent growth opportunities for skilled trained human resource coming from top notch universities from the country and the Watch New Jobs Alerts On Jawatankosong.
ReplyDeleteIn 2016 Petronas announced widespread job cuts, its first ever of that scale, and also said it would cut spending by $50 billion over a four-year Watch Kerja Kosong 2018 At Jawatankosong.
ReplyDeleteThe remaining 14,000 employees have been offered jobs in a new company that is being set up to take over the legacy Malaysia Airlines Watch Kerja Kosong 2018 At Jawatankosong.
ReplyDeleteKUALA LUMPUR, Nov 27 (Reuters) - Malaysian Prime Minister Najib Razak said on Sunday that he will "not necessarily" call a snap election next year, amid talk that he would seek an early vote as splits in the opposition have hobbled efforts to oust him over a long-running financial Watch Jobs in Malaysia 2018 On Jawatankosong.
ReplyDeletethanks for this informative post on What is SCCR and Why is it Needed..
ReplyDeleteNeboshIGC
SCCR is very important for the safety of the products. Hydroponic stores are providing these specialized safety products at low prices.